Energy
Documentation

Version Latest

Compare two SCL files

Compare two SCL files by meaning rather than by XML lines, with every difference as a sentence grouped by part of the station and opened at its place.

State: modelled. Tested on hand-written files and on each public SCL file against itself and after Rename IED; no real pair of releases of a station is public, so none has been compared.

Compare

  1. Run Compare IEC 61850 Files.
  2. Pick the earlier file, then the later file.
  3. A tab opens for the pair. It lists the differences by meaning, grouped by part of the station, each as a sentence, for example:
IED P1 / S1 / LD0 / LLN0 / Data set Trips: Data set member LD0/XCBR1.Pos[ST] was removed
  1. Click a row to open the file where the thing is.

The tab follows both files on disk: save either file and the list updates.

What is compared

PartWhat is compared
IEDsIEDs, access points, logical devices and logical nodes, and their attributes
Data setsData sets and their attributes; members added, removed or reordered
Control blocksGOOSE, Sampled Values and report control blocks and their attributes, such as confRev
InputsInputs added or removed
CommunicationSubnetworks, connected access points and their addresses
SubstationVoltage levels, bays, equipment and their logical node bindings
Data type templatesLogical node, data object, data attribute and enumeration types, and their members

Each difference reads as added, removed, changed order, or changed from one value to another.

The same station written differently (CRLF instead of LF, spaces instead of tabs, without a comment, IEDs in another order) has no differences. Vendor data in Private elements is not compared. Relay setting values are compared by the Relay settings editor, not here.

Try it: compare a station with a later revision in which the APPID of P1 gcb01 went from 0001 to 0002, the member XCBR1.Pos was removed from data set Trips, and confRev of gcb01 went from 1 to 2. The tab lists exactly those three changes.

The same comparison writes the "What" of Record Revision and the change list of Update IED from IID.

Limits

  • The list cannot be exported.
  • The description of a logical node is not among the differences listed.

Not verified

  • A real pair of releases of a station.
  • Which differences a reviewer needs that are not in the list.
  • Windows.

Last reviewed 18 October 2026View as Markdown